Power Quality Analysis Status - Siemens Simatic ET 200SP Manual

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Harmonic
Harmonics are superimposed vibrations deviating from the fundamental frequency of the
supply network (50 Hz or 60 Hz) with an integer multiple of the fundamental frequency.
Harmonics are generated by equipment with a non-linear current–voltage characteristic such
as transformers, gas discharge lamps and power electronics devices.
Harmonic component THD (Total Harmonic Distortion)
The THD defines the ratio of the power of the harmonics to the power of the fundamental
and provides information about the power quality. The value is dimensionless and is stated
as a percentage [%].
The AI Energy Meter HF returns THD+N (Noise) and considers the entire current signal
(DS 163) or voltage signal (DS 161). Interference in the network is not filtered out.
11.1

Power quality analysis status

Information about the power quality status can be found in the measured value "Power
quality analysis qualifier" with the measured value ID 65496.
The bits 0 to 4 in byte 1 to 3 show in status "1" that information has been available since the
last reset, which can be retrieved. The bits 5 to 7 in byte 1 to 3 in status "1" show that the
event is currently active. If the event is not active, "0" is displayed.
The measured value "Network analysis qualifier" has the following structure:
Address Content
Byte 0
Power quali-
ty analysis
qualifier
module
Byte 1
Power quali-
ty analysis
qualifier
phase L1
Byte 2
Power quali-
ty analysis
qualifier
phase L2
Byte 3
Power quali-
ty analysis
qualifier
phase L3
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
Bit 7
Bit 6
Bit 5
Reserved
Reserved
Status of harmonics analysis:
0
1
63
Overcur-
Voltage
Voltage
rent
swell
dip
Event
Event
Event
currently
currently
currently
active
active
active
Bit 4
Bit 3
: No data, no start
D
... 62
: running
D
D
: Completed, data is available
D
Overcur-
Peak
rent
value
current
Event
occurred,
Event
data
occurred,
available
data
available
Power quality analysis functions
11.1 Power quality analysis status
Bit 2
Bit 1
Voltage
Voltage
peak
swell
Event
Event
occurred,
occurred,
data
data
available
available
Bit 0
Voltage
dip
Event
occurred,
data
available
89

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents