Configure The Refresh Rate Of Data Shown On The Display - Emerson Micro Motion 2700 Configuration And Use Manual

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

Configure device options and preferences
Overview
Setting Display Precision determines the precision (number of decimal places) shown on the
display. You can set Display Precision independently for each variable.
Setting Display Precision does not affect the actual value of the process variable.
Procedure
1.
2.
5.1.4

Configure the refresh rate of data shown on the display

Display
ProLink II
ProLink III
Field Communicator Configure > Manual Setup > Display > Display Variable Menu Features > Refresh Rate
Overview
You can set Update Period to control how frequently data is refreshed on the display.
Procedure
Set Update Period to the desired value.
The default value is 200 milliseconds. The range is 100 milliseconds to 10,000 milliseconds
(10 seconds).
80
Select a process variable.
Set Display Precision to the number of decimal places you want shown when the
process variable appears on the display.
For temperature and density process variables, the default value is 2 decimal places.
For all other process variables, the default value is 4 decimal places. The range is
0 to 5.
Tip
The lower the selected precision, the greater the process change must be for it to be reflected
on the display. Do not set Display Precision value too low or too high to be useful.
OFF-LINE MAINT > OFF-LINE CONFG > DISPLAY > RATE
ProLink > Configuration > Display > Update Period
Device Tools > Configuration > Transmitter Display > Display Variables
®
Micro Motion
Model 2700 Transmitters with Analog Outputs

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents