Before you can configure the discrete output, you must configure a channel to operate as a discrete
output.
Important
Whenever you change a discrete output parameter, verify all other discrete output parameters
before returning the flowmeter to service. In some situations, the transmitter automatically loads a
set of stored values, and these values may not be appropriate for your application.
6.4.1

Configure Discrete Output Source

Display
ProLink II
ProLink III
Field Communicator Configure > Manual Setup > Inputs/Outputs > Discrete Output > DO Assignment
Overview
Discrete Output Source controls which flowmeter condition or process condition is reported
via the discrete output.
Procedure
Set Discrete Output Source to the desired option.
The default setting for Discrete Output Source is Flow Direction.
Options for Discrete Output Source
Table 6-9:
Options for Discrete Output Source
Option
Display
Discrete Event 1–
D EV x
(1)
5
(1) Events configured using the enhanced event model.
Configuration and Use Manual
Discrete Output Polarity
Discrete Output Fault Action
OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > SET DO > DO SRC
ProLink > Configuration > Frequency/Discrete Output > Discrete Output > DO Assignment
Device Tools > Configuration > I/O > Outputs > Discrete Output
Label
ProLink II
ProLink III
Discrete
Enhanced Event
1
Event x
Enhanced Event
2
Enhanced Event
3
Integrate the meter with the control system
Condition
Field Commu-
nicator
Discrete
ON
Event x
Discrete out-
put voltage
Site-specific
115