Configure Frequency Output Fault Action And Frequency Output Fault Level - Emerson Micro Motion 2700 Configuration And Use Manual

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

The ON signal may be the high voltage or 0.0 V, depending on Frequency Output Polarity.
Table 6-7:
Polarity
Active High
Active Low
Procedure
Set Frequency Output Maximum Pulse Width as desired.
The default value is 277 milliseconds. You can set Frequency Output Maximum Pulse Width to
0 milliseconds or to a value between 0.5 milliseconds and 277.5 milliseconds. The
transmitter automatically adjusts the value to the nearest valid value.
Tip
Micro Motion recommends leaving Frequency Output Maximum Pulse Width at the default value. Contact
Micro Motion customer service before changing Frequency Output Maximum Pulse Width.
6.3.5
Configure Frequency Output Fault Action and Frequency
Output Fault Level
Display
ProLink II
ProLink III
Field Communicator
Overview
Frequency Output Fault Action controls the behavior of the frequency output if the transmitter
encounters an internal fault condition.
Configuration and Use Manual
Interaction of Frequency Output Maximum Pulse Width and Frequency
Output Polarity
Pulse width
Not available
ProLink > Configuration > Frequency/Discrete Output > Frequency > Freq Fault Action
ProLink > Configuration > Frequency/Discrete Output > Frequency > Freq Fault Level
Device Tools > Configuration > Fault Processing
Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Fault Parameters > FO
Fault Action
Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Fault Parameters > FO
Fault Level
Integrate the meter with the control system
113