Configure Digital Communications Fault Action - Emerson Micro Motion 2700 Configuration And Use Manual

Transmitters with analog outputs
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

4.
5.
6.
6.6.4

Configure Digital Communications Fault Action

Display
ProLink II
ProLink III
Field Communicator Configure > Alert Setup > I/O Fault Actions > Comm Fault Action
Configuration and Use Manual
Set Parity, Stop Bits, and Baud Rate as appropriate for your network.
Set Floating-Point Byte Order to match the byte order used by your Modbus host.
Code
0
1
2
3
See
Table 6-15
for the bit structure of bytes 1, 2, 3, and 4.
Table 6-15:
Bit structure of floating-point bytes
Byte
Bits
1
SEEEEEEE
2
EMMMMMMM
3
MMMMMMMM
4
MMMMMMMM
(Optional) Set Additional Communications Response Delay in "delay units."
A delay unit is 2/3 of the time required to transmit one character, as calculated for
the port currently in use and the character transmission parameters. Valid values
range from 1 to 255.
Additional Communications Response Delay is used to synchronize Modbus
communications with hosts that operate at a slower speed than the transmitter. The
value specified here will be added to each response the transmitter sends to the
host.
Tip
Do not set Additional Communications Response Delay unless required by your Modbus host.
Not available
ProLink > Configuration > Device > Digital Comm Settings > Digital Comm Fault Setting
Device Tools > Configuration > Fault Processing
Integrate the meter with the control system
Byte order
1–2 3–4
3–4 1–2
2–1 4–3
4–3 2–1
Definition
S=Sign
E=Exponent
E=Exponent
M=Mantissa
M=Mantissa
M=Mantissa
131