Enabling Switch (E.g. Sick E100) - Mitsubishi MELSEC-WS0-CPU0 User Manual

Safety controller
Table of Contents

Advertisement

Table 24:
Connection of enabling
switches
Table 25:
Functions of enabling
switches
Note
Connecting devices
4.1.3

Enabling switch (e.g. SICK E100)

Electrical connection: Example from Setting and Monitoring Tool with WS0-XTIO
2 positions,
connected to 24 V
2 positions,
connected to test
output
3 positions,
connected to 24 V
3 positions,
connected to test
output
Function
Testing
Series connection
Discrepancy times
Further information is available in the manual of the enabling switch, SICK E100 or in
the manuals of devices used.
Channel 1: Contact E31 between 24 V and I1
Channel 2: Contact E41 between 24 V and I2
Channel 1: Contact E31 between X1 and I3
Channel 2: Contact E41 between X2 and I4
Channel 1: Contact E13 between 24 V and I5
Channel 2: Contact E23 between 24 V and I6
Channel 3: Contact E31 between 24 V and I7
Channel 4: Contact E41 between 24 V and I8
Channel 1: Contact E13 between 24 V and I1
Channel 2: Contact E23 between 24 V and I2
Channel 3: Contact E31 between X1 and I3
Channel 4: Contact E41 between X2 and I4
Notes
Possible
Not possible
See Setting and Monitoring Tool.
Chapter 4
50