Mitsubishi MELSEC-WS0-CPU0 User Manual page 29

Safety controller
Table of Contents

Advertisement

Product description
Device
Ethernet interface module
CC-Link interface module
ROHS conformity WS0-XTIO
*1
"–" means "any" or "not applicable".
*2
All other modules from product launch onwards.
Note
 You can find the firmware version on the type label of the MELSEC-WS modules in
the field firmware version.
 To be able to use modules with a new firmware version, you will need a new
version of the Setting and Monitoring Tool. For WS-CPU0/1 ≥ V2.01 as well as
WS0-XTIO/XTDI ≥ V2.00 the Designer with at least V1.3.0 is required. This aspect
is to be taken into account on the replacement of devices in existing systems.
 You will find the hardware version of the MELSEC-WS modules in the hardware
configuration of the Setting and Monitoring Tool in the Online state or in the report if
the system was online previously.
 The version of the Setting and Monitoring Tool can be found in the Extras menu
under About.
 For the acquisition of the newest version of the Setting and Monitoring Tool, please
contact your local Mitsubishi representative.
 The function package (Revision 1.xx or Revision 2.xx) must be selected in the
Setting and Monitoring Tool hardware configuration. Function package Revision
2.xx is available with Setting and Monitoring Tool 1.3.0 and higher.
 In order to use function package Revision 2.xx, the respective module must have at
least firmware version V2.00.0. Otherwise you will receive an error message when
you try to upload a configuration using Revision 2.xx to a module with a lower
firmware version.
 Newer modules are downward compatible so that any module can be replaced by a
module with a higher firmware version.
 The same firmware version and function package revision as those of the module
used must be set to the new project after a project stored in the memory plug is
modified.
 You will find the device's date of manufacture at the bottom of the type label in the
format yywwnnnn (yy = year, ww = calendar week, nnnn = continuos serial number
in the calendar week).
Minimum required firmware or software version
WS0-XTIO/
WS0-CPU
WS0-XTDI
V1.11
(Revision 1.xx)
V1.11
(Revision 1.xx)
Hardware version
V1.01 or higher
Chapter 3
Setting and
Monitoring Tool
V1.2.0
V1.2.1
*2
26

Advertisement

Table of Contents
loading

Table of Contents