4. PRE-OPERATION SETIING AND PROCEDURE
/MELSEC;4
No.
Description
Explanation
Indicates the 1/0 status of the corresponding remote I/O station selected
by
the monitor
station number setting switch.
LED
Definition
MON.
YO
Y1
Y2
Y3
Indicates the transmission data of the remote 1/0 station selected by the monitor
Y4
station number setting switch.
Y5
Hernote 1/0
Y6
~
station
monitoring LEDs
Y7
MON.
XO
X1
X2
X3
Indicates the receive data of the remote station selected by the monitor station
X4
number setting switch.
X5
X6
X7
®
Mode setting
Used to switch the link module mode.
switch
Monitor station
Sets the remote 110 station
number to be monitored on the corresponding remote
110
®
number setting
station monitoring LED.
switch
Optical link data
@
transfer
For optical fiber cables.
connector
Twisted pair link
®
data transfer
Used to connect twisted pair cables. Terminal screws are M4.
terminal block
4.3.2 Mode setting switch
Any of the following MINI link operation modes is selected by the
mode setting switch.
For further details of test modes, see Section 4.6.
Switch Position
Mode
Description
Remarks
Online automatic return
Disconnects a faulty remote
VO
station from the system and
0
ONLINE (A.A.)
continues 110 refresh with the other stations if a communication
Online mode
error occurs and automatically returns the faulty station to the
system when the fault is removed.
Online no-automatic return
Online mode
Disconnects a faulty remote
VO
station from the system and
In online no-automatic return mode, all outputs of
1
ONLINE (U.R.)
continues
rio
refresh with the other stations if a communication
the faulty remote
VO
station are switched off
error occurs. The system should be restarted up to return the faulty
independently of its E.C. MODE switch setting
station to the system.
(ON/OFF).
Communication stop at online error detection
Disconnects all remote 110 stations (stops 110 refresh) from the
2
ONLINE (E.S.)
system if a communication error occurs at any remote 110 station.
Online mode
The system should be restarted up to return all stations to the
system.
3
TEST 1
Line check mode
Test mode
Checks for MINI link hardware fault and cable breakage.
Luminous energy check mode
4
TEST 2
Measures luminous energy at the receive terminal of each remote
Test mode
VO
station in an optical data link system.
The TEST LED is lit when 5 is selected. The RUN
5 to 9
- -
Not used
and TEST LEOs are switched off when any of 6 to 9
is selected.
Table 4.1 Mode Setting Switch Positions and Functions
4-4
I