Ws0-4Ro Safety Relay Output Module - Mitsubishi MELSEC-WS0-CPU0 User Manual

Safety controller
Table of Contents

Advertisement

Chapter 12
Table 60:
Data sheet WS0-4R0
107
Technical data
12.2.4

WS0-4RO safety relay output module

Supply circuit (via WS0-CPUx)
Power consumption
Input circuit B1, B2
Input voltage ON
Output circuit (13-14, 23-24, 33-34, 43-44, Y1-Y2, Y3-Y4)
Number of N/O contacts
Number of N/C contacts
Switching voltage
Switching current
Mechanical endurance
Electrical endurance
Minimum contact load with U
DC
Total current
*2
Response time
Type of output
Contact material
Output circuit fusing
Usage category
*1
See Figure 32 or Figure 33.
*2
Time from LOW on B1/B2 to relay drop-out.
Max. 3.2 W
18 V DC ... 30 V DC
4 (13-14, 23-24, 33-34, 43-44)
2 (Y1-Y2, Y3-Y4)
*1
230 V AC
(5 ... 253 V AC)
*1
230 V DC
(5 ... 253 V DC)
10 mA ... 6 A
Min. 10 × 10
6
See Figure 33.
= 24 V
50 mW
n
8 A
30 ms
Potential-free N/O contacts, positively guided
AgSnO
2
6 A (gG), per current path
AC-15: U
250 V, I
e
DC-13: U
24 V, I
e
3 A
e
3 A
e

Advertisement