109
Technical data
Output circuit (Y14, Y24)
Type of output
Number of N/O contacts Y14/24
Output voltage
*3
Output current
Load capacity
General data
Electrical isolation
Supply circuit-input circuit
Supply circuit-output circuit
Input circuit-output circuit
Weight (without packaging)
Operating data
Ambient operating temperature
Storage temperature
Air humidity
Climatic conditions
Mechanical strength
Vibration resistance
Electrical safety IEC 61131-2
Impulse voltage withstand level
(Uimp)
Overvoltage category
Pollution degree
Rated voltage
Enclosure rating housing/terminals
Electromagnetic compatibility
Terminal and connection data
Cross-section of connecting wires
Insulation stripping length
Maximum break-away torque
*3
The total output current is limited. Maximum total current for all safety relay output modules on Y14
and Y24 is I < 80 mA.
N/O contact, connected to internal 24 V DC,
positively guided, current-limited
2
24 V DC (16 ... 30 V DC)
Max. 75 mA
200 nF
No
Yes
Yes
186 g (± 5%)
–25 °C ... 55 °C
–25 °C ... 70 °C
10 % to 95 %, non-condensing
IEC 61131-2, No corrosive gases
5-150 Hz/1 g (EN 60068-2-6)
10-500 Hz/3 g RMS (EN 60068-2-64)
4 kV
II
2 inside, 3 outside
300 V AC
IP 40/IP 20 (IEC 60529)
IEC 61131-2, IEC 61000-6-2, EN 55011 class A
Single-core or finely stranded:
0.2 ... 1.5 mm
2
(24 to 15 AWG)
Finely stranded with ferrules:
0.25 ... 1.5 mm
2
(23 to 15 AWG)
8 mm
0.6 N·m