105
Technical data
General Data
Protection class
Enclosure rating
Ambient temperature in operation
Storage temperature
Humidity
Climatic conditions
Vibration resistance
Shock resistance
Continuous shock
Single shock
Electromagnetic compatibility
System connection
Power input via FLEXBUS+ without
currents to X1 ... X8
Cross-section of connecting wires
Dimensions (W × H × D)
Weight
Safe inputs (I1 ... I8)
Input voltage High
Input voltage Low
Input current High
Input current Low
Input reverse current in case of
ground interruption
*1
Hardware version < V1.10.0
Hardware version ≥ V1.10.0
Switching current (with mechanical
contacts)
Input capacitance
Discrepancy times
Number of inputs
III (IEC 61140)
Terminals: IP 20 (IEC 60529)
Housing: IP 40 (IEC 60529)
–25 ... +55 °C
–25 ... +70 °C
10 ... 95 %, non-condensing
55 °C, 95 % relative. humidity (IEC 61131-2), No
corrosive gases
5-150 Hz/1 g (EN 60068-2-6)
10-500 Hz/3 g RMS (EN 60068-2-64)
10 g, 16 ms (IEC 60068-2-27)
30 g, 11 ms (IEC 60068-2-27)
Class A (IEC 61000-6-2, EN 55011)
Dual level spring clamp terminals
Max. 2 W
Single-core or finely stranded:
0.2 ... 1.5 mm
2
(24 to 15 AWG)
Finely stranded with ferrules:
0.25 ... 1.5 mm
2
(23 to 15 AWG)
22.5 × 106.5 × 120.8 mm
139 g (± 5%)
13 ... 30 V DC
–5 ... +5 V DC
2.4 ... 3.8 mA
–2.5 ... 2.1 mA
Max. 20 mA
1.5 kΩ effective reverse resistance to power supply
Max. 2 mA
14.4 mA at 5 V
3 mA at 24 V
Max. 10 nF + 10 %
4 ms ... 30 s, configurable