● The main line is the longest route distributed from the controller.
NOTE
● The branch lines are the routes branched from the main line.
The total cable length should satisfy the conditions shown in the following table:
The maximum transmission distance (between D and G) will be as follows:
● A mode: 50m
● The maximum length is 50m regardless of the cable conductor cross section (0.3 to 2.0mm
ber of nodes (1 to 256 nodes).
● B mode
Conductor
cross
section
(mm
2
)
0.3
0.5
0.75
1.25
2.0
● C mode
Conductor
cross
Up to 32
section
nodes
(mm
2
)
0.3
570
0.5
0.75
1.25
2.0
● Voltage drop between +24V and 0V is not considered. For this reason, calculate this volt-
NOTE
age drop value, and use a local power supply unit, etc. For a detailed description, refer to
the 'S-LINK V User's Manual.'
● The conductor cross section of the exclusive 4-core flat cable (SL-RCM□) is 0.5mm
● Wire the S-LINK V system while observing the transmission distance specifications de-
scribed above. In addition, use the cables that satisfy the specifications described above.
● To select applicable cables, refer to the 'S-LINK V User's Manual.'
Transmission mode
A
B
C
Number of nodes and maximum transmission length (m)
Up to 224 nodes
200 (full specification for B mode)
Number of nodes and maximum transmission length (m)
Up to 64
Up to 96
nodes
nodes
440
350
710
580
800 (full specification for C mode)
Total cable length
(m)
100
400
1,600
Up to 128
Up to 160
nodes
nodes
300
260
490
420
780
670
System Outline
) and the num-
2
Up to
Up to 224
192nodes
nodes
220
200
370
330
590
530
2
Up to 256
nodes
180
Up to 256
nodes
180
300
480
.
10

Hide quick links: