Setting Of The Master Station - Mitsubishi A1SJ61BT11 User Manual

Control & communication link system master/local module, melsec a
Table of Contents

Advertisement

10 COMMUNICATION BETWEEN THE MASTER STATION AND THE
REMOTE DEVICE STATION

10.1.1 Setting of the master station

A
J61BT11
RUN
ERR.
MST
S MST
LOCAL
CPU R / W
E
SW
R
M / S
R
PRM
O
TIME
R
LINE
L RUN
L ERR.
STATION NO.
MODE
0 : ONLINE (A. R. )
1 : ONLINE (RIM)
2 : OFFLINE
B RATE
0
156K
1
625K
2
2. 5M
3
5M
4
10M
OFF
M / L
CLEAR
1 / 2
1 / 4
ISFM
NC
DA
NC
DB
NC
DG
NC
SLD
NC
(FG)
The settings of the switches on the master station are shown below:
B
156K
625K
R
2. 5M
A
T
5M
E
10M
TEST
T
S0
E
S
S1
T
S2
SD
RD
X10
X 1
C
ON
ON
SW
S MST
1
2
3
HOLD
4
3 / 4
5
2 / 3
6
7
SFM
8
1
2
3
4
5
6
7
8
9
10
Station number setting switch
0 (X10)
Always set "00" for the
0 (X1)
master station
Mode setting switch
0 (online)
Transmission speed setting switch
2 (2.5Mbps)
Condition setting switch
SW
Setting
Description
1
OFF
Master station
2
OFF
3
OFF
4
OFF
Clear
5
OFF
(Invalid when master station)
6
OFF
(Invalid when master station)
7
OFF
8
ON
I/O mode
10 - 2
MELSEC-A

Hide quick links: