4 FUNCTIONS

4.7 Error Invalid Station Function

POINT
If the remote or local station set as the invalid station and also "specified as a reserved
station", the reserved station function has priority.
Address
b15
14
16
H
15
32
H
16
48
H
17
64
H
Master
station
Address
b15
14
0
H
15
0
H
16
0
H
17
0
H
This is a function to treat the remote and local stations that cannot perform data links
due to power off, etc. not as "data-link faulty stations" on the master station and the
local station.
Be careful, however, for errors will not be detected at all if set so.
(1) Setting method
The invalid station specification is performed with parameters (buffer memory
address 14
to 17
H
Turn on the bit corresponding to the station number to be set as invalid.
However, for the remote/local station which occupies more than 2 stations, turn
on the only bit corresponding to the station number set with the module's station
number setting switch.
The buffer memory configuration is shown below. (1 to 64 indicates station
numbers.)
b14
b13
b12
b11
15
14
13
12
31
30
29
28
47
46
45
44
63
62
61
60
(2) Setting example
(a) System configuration example
When specifying the remote station No.3 and local station No.7 as invalid
stations in a system where three remote and two local stations are
connected:
Station No. 1
Station No. 3
Remote station
Remote station
(occupies 2 stations)
(occupies 1 station)
(b) Buffer memory setting example
Turn on the 2nd bit, corresponding to station No. 3, and 6th bit,
corresponding to station No. 7. (Set "68" for address 14
b14
b13
b12
b11
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
).
H
b10
b9
b8
b7
11
10
9
8
27
26
25
24
43
42
41
40
59
58
57
56
Modules to be set as error invalid
Station No. 4
Local station
(occupies 1
station)
b10
b9
b8
b7
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
4 - 23
MELSEC-A
b6
b5
b4
b3
7
6
5
4
23
22
21
20
39
38
37
36
55
54
53
52
Station No. 5
Remote station
(occupies 2 stations)
.)
H
b6
b5
b4
b3
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
b2
b1
b0
3
2
1
19
18
17
35
34
33
51
50
49
Station No. 7
Local station
(occupies 4
stations)
b2
b1
b0
0
0
0
0
0
0
0
0
0
0
0
0