Mitsubishi A1SJ61BT11 User Manual page 19

Control & communication link system master/local module, melsec a
Table of Contents

Advertisement

1 OVERVIEW
Master station
Remote input (RX)
Remote output (RY)
Remote register (RWw)
Remote register (RWr)
(3) Local station communication
The data communication between PC CPUs can be performed in N:N
relationship with bit data (remote input RX and remote output RY) and word data
(remote register)
Link scan
Link scan
Remote register (RWr)
Link scan
Remote register (RWw)
Link scan
(4) Establishing high-speed transmission
When the transmission speed of 10Mbps is set, the link scan time
(communication time with the master station and remote station/local station) is
still at high speed, even when the maximum 64 stations are connected.
Remote I/O (RX, RY) 2048 points ..................................................... 4 ms
Remote I/O (RX, RY) 2048 points
+ remote register (RWw, RWr) 512 points ................ 7 ms
(5) System configurations are possible, according to requirements.
(a) Transmission distance
The total extended distance depends on the transmission speed, but
connections can be made between 100 m (at 10 Mbps) and 1.2 km (at 156
kbps).
(b) Number of connected stations
A maximum of 64 stations, including remote I/O stations, remote device
stations, and local stations can be connected to one master station.
Up to 64 remote I/O stations, 42 remote device stations, and 26 local
stations can be connected. (Refer to Section 2.1.)
Local station
Remote output (RY)
Remote input (RX)
1 - 5
MELSEC-A
Local station
Remote output (RY)
Link scan
Remote input (RX)
Link scan
Remote register (RWr)
Link scan
Remote register (RWw)
Link scan

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aj61bt11A1sj61qbt11Aj61qbt11