4 FUNCTIONS

4.11 Data Link Stop/Restart

M9036
Stop command
Data link stop
M25 (SB0045)
Restart command
Data link restart
M21 (SB0041)
M9036
The data link in the host station can be stopped or restarted.
When the data link is stopped for the master station, the data link for the entire system
stops.
(1) The link special relay used in the program is shown below:
SB0000: Data link restart request
SB0002: Data link stop request
SB0041: Data link restart complete
SB0045: Data link stop complete
(2) A program example to stop/restart the data link is shown below.
This example assumes that the module's first I/O No. is X/Y30.
Relationship between the PC CPU and master station
1
PC CPU
M15
to
M35
to
Program example
2
TO
M0
FROM
M20
FROM
H0003
H05E4 K4M20
SET
RST
SET
RST
TO
H0003 H05E0 K4M0
4 - 27
MELSEC-A
Master station
Link special relay (SB)
5E0
SB000F
to
SB0000
H
5E4
SB004F
to
SB0040
H
Read SB0040 to SB004F status
K1
M2 (SB0002) data-link
M2
stop on
M2 (SB0002) data-link
M2
stop off
M0 (SB0000) data-link
M0
restart on
M0 (SB0000) data-link
M0
restart off
K1
Write to SB0000 to SB000F