Buffer Memory Details - Mitsubishi A1SJ61BT11 User Manual

Control & communication link system master/local module, melsec a
Table of Contents

Advertisement

3 SPECIFICATION

3.5.2 Buffer memory details

Address
Hex.
Dec.
0
0
(Prohibited to use)
H
Number of connected
1
1
H
modules
2
2
Number of retries
H
Number of automatic
3
3
H
return modules
4
4
(Prohibited to use)
H
5
5
(Prohibited to use)
H
Operation specification
6
6
H
when CPU is down
7
to F
7 to 15
(Prohibited to use)
H
H
Reserved station
10
to 13
16 to 19
H
H
specification
Invalid station
14
to 17
20 to 23
H
H
specification
18
to 1F
24 to 31
(Prohibited to use)
H
H
20
to 5F
32 to 95 Station information
H
H
Do not write to areas that are prohibited to use. An error may occur.
POINT
The station information (address 20
becomes valid.
The details of each item shown in Table 3.4 of Section 3.5.1 is described.
(1) Parameter information area
The conditions to perform data link is set.
Also, these can be registered in the E
Table 3.5 Parameter information area list
Item
Set the number of connected remote/local station modules.
(including reserved stations)
Set the number of retries to the communication faulty station.
Set the number of remote/local stations modules that can
return with 1 link scan.
Specify the data-link status when there is a master station PC
CPU error.
Set a reserved station.
Specify an invalid station.
Set the connected remote/local station type.
(a) Number of connected modules
This sets the number of remote/local station modules connected to the
master station (including reserved stations).
This is not a station count.
The setting range is "1 to 64 (modules)."
(b) Number of retries
This sets the number of retries to the remote/local station with a data link
error.
The setting range is "1 to 7(times)."
If the remote/local station cannot recover a normal data link after
performing specified number of retries, the station becomes a "data-link
faulty station."
2
PROM.
Description
to 5F
) for the specified "number of connected" stations
H
H
3 - 20
MELSEC-A
Default
64
3
1
0 (Stop)
0 (No specification)
0 (No specification)
Station type: Remote I/O
station
Number of occupied
stations: 1
Station numbers: 1 to 64