Mitsubishi A1SJ61BT11 User Manual page 175

Control & communication link system master/local module, melsec a
Table of Contents

Advertisement

8 PROGRAMMING
Number
Name
SW0049
Temporary error invalid
(649
)
station request result
H
Temporary error invalid
SW004B
station canceling request
(64B
)
H
result
SW004D
Line test request result
(64D
)
H
SW004F
Parameter setting test
(64F
)
request result
H
SW0060
Mode setting switch status
(660
)
H
SW0061
Station number setting
(661
)
switch status
H
SW0062
Condition setting switch
(662
)
status
H
SW0064
No. of retries setting
(664
)
information
H
SW0065
No. of automatic return
(664
)
stations information
H
SW0066
Delay timer information
(666
)
H
SW0067
Parameter information
(667
)
H
SW0068
Host parameter status
(668
)
H
: Link special relay added to the function version B or later
Stores the execution results of the temporary error invalid station
request specification by SB0004.
0
: Normal
Other than 0 : Stores error code (Refer to Section 13.3.)
Stores the execution results of the temporary error invalid station
canceling request specification by SB0005.
0
: Normal
Other than 0 : Stores error code (Refer to Section 13.3.)
Stores the execution results of the line test request specification by
SB0008.
0
: Normal
Other than 0 : Stores error code (Refer to Section 13.3.)
Stores the execution results of the parameter setting test request by
SB0009.
0
: Normal
Other than 0 : Stores error code
Stores the setting status of the mode setting switch.
0: Online (remote net mode)
1: Online (remote I/O net mode)
2: Offline
3: Line test 1
4: Line test 2
5: Parameter verification test
6: Hardware test
Stores the station number setting switch's setting status.
0
: Master station
1 to 64
: Local station
The setting status of the condition setting switch (DIP switch) is
stored.
0: OFF
1: ON
b15
b8 b7 b6 b5 b4 b3 b2 b1 b0
0
to
0
Stores the number of retries setting information when responding to
an error.
1 to 7 (times)
Stores the number of automatic return stations setting information
during one link scan.
1 to 10 (modules)
Stores the delay time setting information.
The parameter information area to be used is stored.
1: Buffer memory (data link startup by Yn6)
2
2: E
PROM (data link startup by Yn8)
Parameter setting status is stored.
0
: Normal
Other than 0 : Stores error code (Refer to Section 13.3.)
8 - 17
Description
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
MELSEC-A
Availability
(
: available,
: not available )
Online
Offline
Master
Local
station
station

Hide quick links: