3 SPECIFICATION
(6) Data link startup by buffer memory parameter normal completion: Xn6
Indicates normal completion in data link startup requested by the buffer-memory
parameter data link startup request (Yn6).
(a) When (Yn6) is turned on, the parameter contents at the (address 0
buffer memory are checked. If the check result is normal data link is started
automatically.
(b) When data link is normally started, the signal for "data link startup by buffer-
memory parameter normal completion" (Xn6) is turned on.
(c) (Xn6) is turned off by turning off (Yn6).
Data link startup by buffer-memory
parameter normal completion (Xn6)
Parameter setting status (Xn2)
Host station parameter status
(SW0068)
Buffer-memory parameter
data link startup request (Yn6)
(7) Data link startup by buffer memory parameter error completion: Xn7
Indicates abnormal completion in data link startup requested by the buffer-
memory parameter data link startup request (Yn6).
(a) When (Yn6) is turned on, the parameter contents at the (address 0
buffer memory are checked. If error is detected the signal for "data link startup
by buffer-memory parameter abnormal completion" (Xn7) is turned on.
(b) Parameter setting status (Xn2) is turned on and the error code is stored in the
host station parameter status in buffer memory (SW0068).
(c) (Xn7) is turned off by turning off (Yn6).
Data link startup by buffer-memory
parameter error completion (Xn7)
Parameter setting status (Xn2)
Host station parameter status
(SW0068)
Buffer-memory parameter
data link startup request (Yn6)
OFF
Start processing
OFF
3 - 11
MELSEC-A
0
Start
processing
0
Error code
to 5F
) in
H
H
to 5F
) in
H