7 DATA LINK PROCEDURE
Item
When the hardware version of the master module is as follows:
AJ61BT11
AJ61QBT11
AISJ61BT11 : Hardware version D or later
AISJ61QBT11 : Hardware version D or later
110 Ω ± 5 %, 1/2 W × 4
(connect across DA-DG and DB-DG) ..........Both ends
[connection]
Terminating resistance
(connection method)
When the hardware version of the master module is other than
those stated above, connect the resistance of 110 Ω furnished
with the master module.
Refer to Section 7.5 for connection method.
Terminal block..... Commercial terminal block
Connector ........... Connector NECA4202 for FA sensor
T-Branch terminal
block/connector
CC-Link dedicated cable/ Version 1.10 compatible CC-Link dedicated cable
(terminating resistance of 110 Ω is used)
Max. trunk line length,
T-junction interval, and
Transmission
station-to-station cable
length
1: 1 m or longer when the system is configured only with the remote I/O stations and remote device stations.
2: 2 m or longer when the system is configured only with the local stations and intelligent device stations.
Terminating
resistance
R
(Branch line length of 8 m or shorter)
Specification
: Hardware version C or later
: Hardware version C or later
DA
110
DB
110
DG
SLD
FG
(ICE947-5-2) or equivalent is recommended.
(NECA: Nippon Electric Control Equipment
Industries Association)
Max. trunk
T-junction
speed
line length
interval
625kbps
100m
Limitless
156kbps
500m
Max. trunk line length (not including branch line length)
2
2
Master station
2
R
1
L/I
R
1
R
Station-to-station cable length
for remote I/O stations or
remote device stations 1
30 cm or longer
T-junction interval
1
1
R
R
R
2
L/I
R
: Indicates the remote I/O station or remote device station.
L/I
: Indicates the local station or intelligent device station.
7 - 11
Remark
Use commercial terminating resistances of
110 Ω ± 5 % and 1/2 W.
[Resistance model name]
(Example: ERDS1TJ111 Matsushita Electronic
Components Co., Ltd.)
Use of the resistances of 110 Ω and 130 Ω
furnished with the master and local modules is
prohibited.
The method to connect the terminating
resistance across DA-DG and DB-DG is also
acceptable.
If possible, do not remove the cover of the
cable on the trunk line side.
Station-to-station cable length for
master local station or intelligent device
station and its front and rear stations 2
1 m or longer ( 1)/
2 m or longer ( 2)
2
2
2
L/I
L/I
R
2
2
1
1
1
R
R
R
(Branch line length of 8 m or shorter)
MELSEC-A
Terminating
resistance
1
R
R