Condition Setting - Mitsubishi A1SJ61BT11 User Manual

Control & communication link system master/local module, melsec a
Table of Contents

Advertisement

7 DATA LINK PROCEDURE

7.7.4 Condition setting

Number Description
Station
OFF : Master/local station
SW1
type
ON : Standby master station
SW2
(Unusable)
SW3
(Unusable)
Input data
status of
OFF : Clear
SW4
the data
ON : Hold
link faulty
station
Number of
occupied
stations
1 stations
Number of
SW5
2 stations 1
occupied
SW6
stations
3 stations 1
4 stations
SW7
(Unusable)
Module
OFF : Intelligent mode
SW8 2
mode
ON : I/O mode
1 : The AJ61BT11 of hardware version F or later and the A1SJ61BT11 of hardware version G or later are compatible with this setting.
For other than the above, only SW5 is used to set the number of occupied stations.
OFF : 1 station occupied
ON : 4 stations occupied
Keep SW6 OFF as it is unusable.
2 : Choose the intelligent mode when:
(1) Intelligent device station is connected.
To check whether the module connected is an intelligent device station or not, refer to the user's manual of the corresponding
module, e.g. AJ65BT-R2(N), AJ65BT-G4, AJ65BT-D75P2-S3, etc.; or
(2) Transient transmission is used at a local station or the like.
The setting method of the condition setting switch (DIP switch) is shown in Table 7.2.
Table 7.2 Condition setting
Switch status
SW5
SW6
OFF
OFF
OFF
ON
ON
ON
ON
OFF
Master station
OFF (station number 0)
When setting all input data from the data-link faulty station to all off. (Refer
OFF
to Section 4.9.)
When keeping the input data from the data-link faulty station in the status
ON
right before the error. (Refer to Section 4.9.)
Setting not necessary (OFF)
When intelligent mode : OFF
When I/O mode
: ON
7 - 15
MELSEC-A
Setting
Local station
OFF (station number 1 to 64)
Always OFF
Always OFF
Remote input RX
Remote output RY
Remote register RWw
Remote register RWr
Remote input RX
Remote output RY
Remote register RWw : 8 points
Remote register RWr
Remote input RX
Remote output RY
Remote register RWw : 12 points
Remote register RWr
Remote input RX
Remote output RY
Remote register RWw : 16 points
Remote register RWr
Always OFF
: 32 points
: 32 points
: 4 points
: 4 points
: 64 points
: 64 points
: 8 points
: 96 points
: 96 points
: 12 points
: 128 points
: 128 points
: 16 points