7 DATA LINK PROCEDURE
7.8.2 Checking connection and communication status with specific remote station/local
station (Line Test 2)
Connect only the modules subject of the test to
the master module, or power supply on only the
test station.
Set the station number setting switch of the
master module to the station number of the
module to be tested.
Set the master module's "mode setting switch"
to "4".
For AJ61BT11:
Operate the RUN/STOP key switch and the
RESET key switch of ACPU in the following
procedure:
Reset the module using the
RESET key switch.
The test is started after approximately four
seconds. (The "TEST" LED turns on.)...Only AJ61BT11
Continued to the next page
Confirms if data link can be performed normally with specific remote and local stations.
There is no need to set parameters.
Perform Line Test 2 by following the procedure below:
Start
ACPU
AJ61
BT11
Set the RUN/STOP key
switch to "STOP".
.........Set "0 (online)" at local stations.
For A1SJ61BT11:
AnSCPU
A2ASCPU
Operate the RUN/STOP key switch of the
AnS/A2ASCPU in the following procedure:
7 - 18
MELSEC-A
A1S
J61
BT11
STOP
RESET
STOP