Resetting Alarm Message; Bypassing Detectors - Bosch MPC-xxxx-C Series User Manual

Panel controller
Hide thumbs Also See for MPC-xxxx-C Series:
Table of Contents

Advertisement

Panel Controller
1.
2.
10.7

Resetting alarm message

Notice!
The detector can only be reset once the Reset time has elapsed, generally after half of the
verification time.
When an element is reset, its initial status is restored. The activation of transmission devices
such as fire department or extinguishing devices is reset.
Depending on the configuration, three different variants are offered for resetting:
To reset an alarm message, select either
If different elements are offered for resetting:
1.
2.
3.
TEXT
If a list field is marked with an R, the process of resetting is not yet complete for this element.
If an element cannot be reset, it will continue to be displayed in the list.
After the successful resetting of all elements, the standby display is displayed.
10.8

Bypassing detectors

To bypass a detector that has triggered an alarm:
Bosch Sicherheitssysteme GmbH
To forward the alarm to external stations, select Manual alarm.
Select OK to confirm the operation.
The alarm is forwarded to the fire department:
In the LED display, the "Transmission Device activated" signal light turns red.
Standard
Resetting all message types of the same message type:
All types of messages within the selected message type, such as Fire, are reset.
Resetting all elements that are not in the normal state
Displaying a submenu with four different selection options
Each displayed component can be reset individually:
This panel
To reset all elements that are not in the normal state
All elements in this event
to reset all elements that have triggered a fire alarm, for example
Logical zone
a list of the logical zones is displayed
Detector
a list of the detectors is displayed
Reset on the message display
or
The alarm message and Reset in the detailed view:
Depending on the variant that is offered (see above), all elements that are not in the
alarm state or all types of message within the same message type are reset.
Select an element. At the menu items Zone and Detector, a list with all the logical zones
and detectors concerned appears.
Select the list field you require. Refer to Scrolling through lists, page 27 for information on
how to scroll forward and backward through a list.
The list field is marked.
Select Reset.
The selected element / element group is reset.
R
User Guide
Fire alarm | en
49
2017.09 | 7.0 | F.01U.258.929