Zone Information

13.1

Day Alarm Information

Item
Day Alarm Zones
This location has four programming options. You can select any combination of the options by
programming a single value. Calculate this value by adding the option bit numbers together.
Day Alarm allows some zones to be monitored when the system is disarmed. Indications are
available at any of the programmable outputs, including the codepad buzzer. This function
accommodates latching and non-latching Day Alarm Output Event Types.
When the system is armed in AWAY Mode, STAY Mode 1, or STAY Mode 2, zones programmed
as Day Alarm Zones activate the sirens and report just as non-Day Alarm Zones do. When Day
Alarm is activated, it ignores any zone Pulse Count settings programmed for that zone (that is,
the zone Pulse Count is only relevant when the system is armed).
Example
You can set up a Day Alarm at the front door of a shop with a pressure mat or electronic beam
that is activated when a customer enters the shop. When a customer walks on the pressure
mat or breaks the electronic beam, the codepad buzzer beeps.
13.1.1

Day Alarm Resetting

An output that is programmed for Day Alarm Resetting operates when a zone programmed for
Day Alarm is activated. The output is reset after the zone is resealed. This occurs only when
the system is disarmed. Refer to 0,14 Day Alarm Resetting in Output Event Types, page 123
for more information.
13.1.2

Day Alarm Latching

An output that is programmed for Day Alarm Latching operates when a zone programmed for
Day Alarm is activated. The zone indicator and the latching output resets when [AWAY] is
pressed. This occurs only when the system is disarmed. Refer to 0,15 Day Alarm Latching in
Output Event Types, page 123 for more information.
13.1.3

Day Alarm Operation

If a zone is programmed for Day Alarm, the zone can be isolated in the normal way so that it
does not register as a Day Alarm Zone when the system is disarmed. You can use only Zones 1
to 4 as Day Alarm Zones.
You can program the STAY indicator to indicate whether Day Alarm is turned on or off by
selecting Option 8 in Location 496 (refer to Consumer Options 1, page 141). When Day Alarm
is on, the STAY indicator flashes once every 3 seconds.
You can program an output to mimic a zone for monitoring Zones 5 to 8. Refer to Output Event
Types, page 123.
To turn Day Alarm on:
Press and hold [4] until three beeps sound.
To turn Day Alarm off:
Press and hold [4] until two beeps sound.
Bosch Security Systems, Inc.
Location
Option
0265
1 = Zone 1
2 = Zone 2
4 = Zone 3
8 = Zone 4
Installation Guide
Zone Information | en
Default
New
0