Panel Controller
16
Maintenance – walktest
This chapter contains information about the following points:
A walktest is indicated by a yellow LED display on the panel.
Caution!
Alarm or fault messages from detectors switched to walktest are not forwarded to
!
transmission devices or extinguishers.
Notice!
If a signaling device is activated during a walktest, it emits a different signal tone to the one it
emits in the alarm state.
16.1

Walktest groups

The following options are available for switching elements to walktest:
There are 12 pre-defined walktest groups. The number of possible walktest groups is
predefined: January to December.
Example:
Detectors which are to be tested in May, can be grouped together in a group called May.
New elements can be added to a group, and elements that have already been added can be
removed.
Notice!
Even if the elements in a group (e.g. January) have been completely deleted, this group will
still be displayed in the list.
16.1.1

Adding or deleting elements

In order to add elements to a walktest group or remove elements from it:
1.
2.
3.
4.
Bosch Sicherheitssysteme GmbH
Walktest groups, page 73
Starting and ending walktest, page 75
Ending walktest for all elements, page 75
Displaying tested or untested elements, page 76
Assigning tested elements to a walktest group, page 76
Select individual elements from lists and/or
Select previously defined walktest groups consisting of at least one element.
In the start menu, select Maintenance
Walktest
Create / Change walktest group
A list of the walktest groups is displayed.
Select a walktest group, e.g. February.
You can choose from a number of options:
Delete all: Delete all elements in the selected group.
Show / Change: Delete all elements in the selected walk test group and delete
individual elements.
Add: Display all elements that have not yet been assigned to a walk test group, and
add individual elements.
Cancel: Cancel the operation.