To change the name of the input or output group:
1.
2.
16.2

Starting and ending walktest

Notice!
The information about the date and time of every walktest is stored in the history log. You can
print this information on a printer. See Maintenance – history log, page 77.
16.2.1

Starting the walktest

To select the elements for the walktest and to switch them to walktest:
1.
2.
3.
4.
Notice!
If you select the element category Loop, Logical zone, Detector or Walktest group, you will
be asked to select the type of walk test. Select Sequential walktest to check each individual
sensor (optical, chemical or thermal) of the detectors you are testing, or select Simultaneous
walktest to test combination detectors using a test device with combined trigger substances
for simultaneous testing of multiple sensors.
Example:
1.
2.
3.
4.
16.2.2

Ending the walktest

To end the walktest for this walktest group:
1.
2.
16.3

Ending walktest for all elements

To end the walktest for all walktest groups and elements:
Bosch Sicherheitssysteme GmbH
Select Add.
The selected element is added to the selected walktest group.
Overwrite the name; see Entering numbers and text, page 29.
Select OK.
The new name is confirmed.
In the start menu, select Maintenance
Walktest
Start / End walktest
Various element categories are displayed.
Select:
More... to display further categories or
one of the displayed categories or
Select by number and enter the number of the element into the search screen; see
also Search Function/Element, page 29.
Select Walktest group.
Select Sequential walktest or Simultaneous walktest
A list of walktest groups is displayed. Refer to Scrolling through lists, page 27 for
information on how to navigate through a list.
Select the list field you require.
The field is marked.
Select On.
The selected walktest group is switched to walktest.
Mark the selected walktest group.
Select Off.
User Guide
Maintenance – walktest | en