Saving And Transferring Data Using The Mmc - Siemens SINAMICS G110D Operating Instructions Manual

Hide thumbs Also See for SINAMICS G110D:
Table of Contents

Advertisement

Commissioning
5.9 Backup data and storage
5.9.2

Saving and transferring data using the MMC

The SD/MMC memory card as a medium for backing up and transferring data
You can save a parameter set on the memory card and transfer it to other Inverters, for
example, to identically parameterized Inverters or to transfer the settings after an Inverter
has been replaced.
Note
Location of memory card holder
The memory card holder on the SINAMICS G110D is located under the top cover of the
Control Unit housing. The memory card must be installed prior to the electrical installation of
the Inverter. When re-assembling the housing, it is important to ensure that the seals are
replaced correctly because if the seal are not fitted incorrectly it will adversely affect the IP
rating of the Inverter.
Data backup
The SD/MMC is a removable, non-volatile flash memory for the parameter sets of an Inverter
and does not require a power supply. For instance, this can be used to transfer parameter
settings to a new Inverter after the previous one was replaced.
We recommend that memory card MMC (Order No.: 6SL3254-0AM00-0AA0) should be
used.
Prerequisites for transferring data sets from the SD/MMC to a different inverter
The Control Unit to which the parameter set is transferred must be of the same type and
have the same firmware release as the source Control Unit. (Same 'type' means: The same
Order No.)
Backup the parameters on the SD/MMC memory card (upload)
Parameter
Insert
SD/MMC
A0564
P0003 = 3
P0010 = 30
P0802 = 2
76
Description
This alarm means that the SD/MMC was inserted while the device was in operation
and that no SD/MMC was inserted when the inverter was started.
3: Access level 3
30: Parameter transfer
2: Start data transfer from the EEPROM to the SD/MMC. "RDY" LED flashes.
If the upload procedure is successful, P0010 and P0802 are set to 0 and the "RDY"
LED lights up.
If the download procedure is unsuccessful, F0061 or F0062 is displayed and the
LED "SF" (red) lights up. In this case, make another attempt to transfer data.
Operating Instructions, 2009-05-15, A5E02385577A AB
SINAMICS G110D

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents