Functions
6.2 Inverter Control
Table 6- 9
Enable
Table 6- 10
Parameter
P0700 = 2
P0727 = 2
P0701 = 1
P0702 = 2
P0703 = 12
88
Function table
Motor ON /
signal
CW
0
Not
relevant
1
0→1
1
0
1
0
1
1
Parameterizing the function
Description
Controls the motor using the digital inputs of the inverter
Three-wire control, method 1
The enable signal to power-up the motor is issued with digital input 0
Further options:
The enable signal can be issued with any other digital input, e.g. with digital input 3
via P0704 = 1
CW rotation is activated with digital input 1
Further options:
CW rotation can be activated with any other digital input, e.g. with digital input 3 via
P0704 = 2
CCW rotation is activated with digital input 2
Further options:
CCW rotation can be activated with any other digital input, e.g. with digital input 3
via P0704 = 12
Motor ON /
Function
CCW
Not
OFF1: The motor decelerates to a standstill
relevant
0
The motor accelerates to the setpoint
0→1
The motor accelerates to the inverted setpoint
0
No effect on the direction of rotation.
1
OFF1: The motor decelerates to a standstill
Operating Instructions, 2009-05-15, A5E02385577A AB
SINAMICS G110D

Hide quick links:

Advertisement

Table of Contents
loading