Example S7 script and ladder logic
The following is an example S7 script which the PLC will use to communicate with the
Inverter.
Baustein:
FC2
Netzwork:
1
U
"START"
=
"G110D _ FAST"
Netzwork:
2
U
"G110D _ DI3"
FP
"EdgeDI3"
S
"ConveyorOccupied"
Netzwork:
3
U
"G110D _ DI1"
U
"NextConveyorOccupied"
-
"G110D _ SLOW"
Netzwork:
4
UN
"NextConveyorOccupied"
=
"G110D _ QSdisable"
Netzwork:
5
UN
"G110D _ DI0"
FN
"EdgeDI0"
R
"ConveyorOccupied"
Figure 5-24
Example S7 script
The following is an example ladder logic diagram.
SINAMICS G110D
Operating Instructions, 2009-05-15, A5E02385577A AB
Conveyor application parameters
Setting Description
22
Digital input DI0 set to Quick Stop source 1 allowing DI0 to be used as Quick
Stop input
1
Transfers parameter values from RAM to EEPROM
Example application
Start conveyor
Generate message occupied
Switch from FAST to SLOW
Wait for following conveyor
Generate message occupied
Commissioning
5.8 Example application