Shock and vibration
Do not drop the Inverter or expose to sudden shock. Do not install the Inverter in an area
where it is likely to be exposed to constant vibration.
Electromagnetic radiation
Do not install the Inverter near sources of electromagnetic radiation.
Atmospheric pollution and water
When fully assembled the inverter has an IP65 rating. This means that the inverter is totally
protected against dust and low pressure jets of water. Any unused connections should be
covered with the correct sealing caps to ensure the IP65 rating.
4.7

SINAMICS G110D Specifications

SINAMICS G110D specifications
Table 4- 1
Rated Output, Input and Fuses
Product
Frame
size
6SL3511-...
0PE17-5AM0
A
0PE21-5AM0
A
0PE23-0AM0
A
0PE24-0AM0
B
0PE25-5AM0
C
0PE27-5AM0
C
For further technical information, please refer to the Operating Instructions.
Group fusing
Group fusing is where one circuit breaker or fuse is intended to provide protection for two or
more devices. The protection device is called a branch circuit protection (BCP) device.
For more information, please read the following FAQ:
SINAMICS G110D
Operating Instructions, 2009-05-15, A5E02385577A AB
Rated output
HO
Rated output
current
kW
hp
A
0.75
1
2.3
1.5
1.5
4.3
3
4
7.7
4
5
10.2
5.5
7.5
13.2
7.5
10
19
4.7 SINAMICS G110D Specifications
Fuse
Rated input
3NA3...
current
A
A
Type
2.0
10
803
-
3.9
10
803
-
7.0
16
805
-
9.1
20
807
-
12.2
20
807
-
17.9
32
812
-
Connection
Circuit breakers
Order Number
3RV1021-1FA10
3RV1021-1JA10
3RV1021-4AA10
3RV1021-4BA10
3RV1031-4EA10
3RV1031-4FA10
37