Siemens SIPROTEC Manual page 698

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Appendix
A.7 Settings
Addr.
Parameter
3187A
XserCap
3201
FCT Telep. E/F
3202
Line Config.
3203A
Send Prolong.
3207A
Delay for alarm
3208
Release Delay
3209A
TrBlk Wait Time
3210A
TrBlk BlockTime
3212A
EF TRANSBLK DIS
3401
AUTO RECLOSE
3402
CB? 1.TRIP
3403
T-RECLAIM
3403
T-RECLAIM
3404
T-BLOCK MC
3406
EV. FLT. RECOG.
3407
EV. FLT. MODE
3408
T-Start MONITOR
3409
CB TIME OUT
3410
T RemoteClose
3411A
T-DEAD EXT.
3420
AR WITH DIFF
3421
AR w/ SOTF-O/C
3422
AR w/ DIST.
3423
AR WITH I.TRIP
3424
AR w/ DTT
3425
AR w/ BackUpO/C
3426
AR w/ W/I
3427
AR w/ EF-O/C
3430
AR TRIP 3pole
3431
DLC / RDT
3433
T-ACTION ADT
3434
T-MAX ADT
3435
ADT 1p allowed
3436
ADT CB? CLOSE
698
Function
C
Earth Fault O/C
1A
0.000 .. 600.000 Ω
5A
0.000 .. 120.000 Ω
Teleprot. E/F
ON
OFF
Teleprot. E/F
Two Terminals
Three terminals
Teleprot. E/F
0.00 .. 30.00 sec
Teleprot. E/F
0.00 .. 30.00 sec
Teleprot. E/F
0.000 .. 30.000 sec
Teleprot. E/F
0.00 .. 30.00 sec; ∞
Teleprot. E/F
0.00 .. 30.00 sec
Teleprot. E/F
YES
NO
Auto Reclose
OFF
ON
Auto Reclose
YES
NO
Auto Reclose
0.50 .. 300.00 sec
Auto Reclose
0.50 .. 300.00 sec; 0
Auto Reclose
0.50 .. 300.00 sec; 0
Auto Reclose
with PICKUP
with TRIP
Auto Reclose
Stops AutoRecl
starts 3p AR
Auto Reclose
0.01 .. 300.00 sec
Auto Reclose
0.01 .. 300.00 sec
Auto Reclose
0.00 .. 300.00 sec; ∞
Auto Reclose
0.50 .. 300.00 sec; ∞
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Auto Reclose
WITHOUT
DLC
Auto Reclose
0.01 .. 300.00 sec; ∞
Auto Reclose
0.50 .. 3000.00 sec
Auto Reclose
YES
NO
Auto Reclose
YES
NO
Setting Options
Default Setting
0.000 Ω
0.000 Ω
ON
Two Terminals
0.05 sec
10.00 sec
0.000 sec
0.04 sec
0.05 sec
YES
ON
NO
3.00 sec
3.00 sec
1.00 sec
with TRIP
starts 3p AR
0.50 sec
3.00 sec
0.20 sec
∞ sec
YES
YES
YES
YES
YES
YES
YES
YES
YES
WITHOUT
0.20 sec
5.00 sec
NO
NO
C53000-G1176-C169-5, Release date 02.2011
Comments
Reactance X of series capacitor
Teleprotection for Earth Fault
O/C
Line Configuration
Time for send signal prolongation
Unblocking: Time Delay for
Alarm
Time Delay for release after
pickup
Transient Block.: Duration exter-
nal flt.
Transient Block.: Blk.T. after ext.
flt.
EF transient block by DIS
Auto-Reclose Function
CB ready interrogation at 1st trip
Reclaim time after successful AR
cycle
Reclaim time after successful AR
cycle
AR blocking duration after
manual close
Evolving fault recognition
Evolving fault (during the dead
time)
AR start-signal monitoring time
Circuit Breaker (CB) Supervision
Time
Send delay for remote close
command
Maximum dead time extension
AR with differential protection ?
AR with switch-onto-fault over-
current ?
AR with distance protection ?
AR with intertrip ?
AR with direct transfer trip ?
AR with back-up overcurrent ?
AR with weak infeed tripping ?
AR with earth fault overcurrent
prot. ?
3pole TRIP by AR
Dead Line Check / Reduced
Dead Time
Action time
Maximum dead time
1pole TRIP allowed
CB ready interrogation before re-
closing
SIPROTEC, 7SD5, Manual