Siemens SIPROTEC Manual page 164

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Functions
2.5 Distance Protection
Figure 2-63
Polarised MHO characteristic
As is the case with all characteristics that pass through the origin of the coordinate system, the MHO charac-
teristic boundary around the origin itself is also not defined as the measured voltage is zero or too small to be
evaluated in this case. For this reason, the MHO characteristic is polarized. The polarization determines the
lower zenith of the circle, i.e. the lower intersection of the diameter line with the circumference. The upper zenith
which is determined by the reach setting Z
circuit voltage is disturbed by transients; the voltage memorized prior to fault inception is therefore used for po-
larization. This causes a displacement of the lower zenith by an impedance corresponding to the memorized
voltage (refer to Figure 2-64). When the memorized short-circuit voltage is too small, an unfaulted voltage is
used. In theory, this voltage is perpendicular to the voltage of the faulted loop for both phase-to-earth loops as
well as phase-to-phase loops. This is taken into account by the calculation by means of a 90° rotation. The un-
faulted loop voltage also causes a displacement of the lower zenith of the MHO characteristic.
164
Basic shape of an MHO characteristic
remains unchanged. Immediately after fault inception, the short-
r
C53000-G1176-C169-5, Release date 02.2011
SIPROTEC, 7SD5, Manual

Advertisement

Table of Contents
loading

Table of Contents