Appendix
A.7 Settings
Addr.
Parameter
302
CHANGE
402A
WAVEFORMTRIGGER
403A
WAVEFORM DATA
410
MAX. LENGTH
411
PRE. TRIG. TIME
412
POST REC. TIME
415
BinIn CAPT.TIME
610
FltDisp.LED/LCD
615
Spont. FltDisp.
625A
T MIN LED HOLD
640
Start image DD
1103
FullScaleVolt.
1104
FullScaleCurr.
1105
Line Angle
1106
OPERATION POWER
1107
P,Q sign
1111
x'
1111
x'
1112
c'
1112
c'
1113
Line Length
1113
Line Length
1114
Tot.Line Length
1114
Tot.Line Length
1116
RE/RL(Z1)
1117
XE/XL(Z1)
1118
RE/RL(> Z1)
1119
XE/XL(> Z1)
1120
K0 (Z1)
1121
Angle K0(Z1)
1122
K0 (> Z1)
686
Function
C
Change Group
Group A
Group B
Group C
Group D
Binary Input
Protocol
Osc. Fault Rec.
Save w. Pickup
Save w. TRIP
Start w. TRIP
Osc. Fault Rec.
Fault event
Pow.Sys.Flt.
Osc. Fault Rec.
0.30 .. 5.00 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
Osc. Fault Rec.
0.05 .. 0.50 sec
Osc. Fault Rec.
0.10 .. 5.00 sec; ∞
Device
Target on PU
Target on TRIP
Device
NO
YES
Device
0 .. 60 min; ∞
Device
image 1
image 2
image 3
image 4
image 5
image 6
P.System Data 2
0.4 .. 1200.0 kV
P.System Data 2
10 .. 10000 A
P.System Data 2
10 .. 89 °
P.System Data 2
0.2 .. 5000.0 MVA
P.System Data 2
not reversed
reversed
P.System Data 2
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
P.System Data 2
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
P.System Data 2
1A
0.000 .. 100.000 µF/km
5A
0.000 .. 500.000 µF/km
P.System Data 2
1A
0.000 .. 160.000 µF/mi
5A
0.000 .. 800.000 µF/mi
P.System Data 2
0.1 .. 1000.0 km
P.System Data 2
0.1 .. 650.0 Miles
P.System Data 2
0.1 .. 1000.0 km
P.System Data 2
0.1 .. 650.0 Miles
P.System Data 2
-0.33 .. 10.00
P.System Data 2
-0.33 .. 10.00
P.System Data 2
-0.33 .. 10.00
P.System Data 2
-0.33 .. 10.00
P.System Data 2
0.000 .. 4.000
P.System Data 2
-180.00 .. 180.00 °
P.System Data 2
0.000 .. 4.000
Setting Options
Default Setting
Group A
Save w. Pickup
Fault event
2.00 sec
0.25 sec
0.10 sec
0.50 sec
Target on PU
NO
0 min
image 1
400.0 kV
1000 A
85 °
692.8 MVA
not reversed
0.1500 Ω/km
0.0300 Ω/km
0.2420 Ω/mi
0.0484 Ω/mi
0.010 µF/km
0.050 µF/km
0.016 µF/mi
0.080 µF/mi
100.0 km
62.1 Miles
100.0 km
62.1 Miles
1.00
1.00
1.00
1.00
1.000
0.00 °
1.000
C53000-G1176-C169-5, Release date 02.2011
Comments
Change to Another Setting
Group
Waveform Capture
Scope of Waveform Data
Max. length of a Waveform
Capture Record
Captured Waveform Prior to
Trigger
Captured Waveform after Event
Capture Time via Binary Input
Fault Display on LED / LCD
Spontaneous display of flt.an-
nunciations
Minimum hold time of lachted
LEDs
Start image Default Display
Measurement: Full Scale Voltage
(100%)
Measurement: Full Scale Current
(100%)
Line Angle
Operational power of protection
zone
P,Q operational measured values
sign
x' - Line Reactance per length
unit
x' - Line Reactance per length
unit
c' - capacit. per unit line len.
µF/km
c' - capacit. per unit line len.
µF/mile
Line Length
Line Length
Total Line Length
Total Line Length
Zero seq. comp. factor RE/RL for
Z1
Zero seq. comp. factor XE/XL for
Z1
Zero seq. comp.factor RE/RL(>
Z1)
Zero seq. comp.factor XE/XL(>
Z1)
Zero seq. comp. factor K0 for
zone Z1
Zero seq. comp. angle for zone
Z1
Zero seq.comp.factor K0,higher
zones >Z1
SIPROTEC, 7SD5, Manual