Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Functions
2.18 Synchronism and Voltage Check (optional)
Synchronism conditions for automatic reclosure
Addresses 3510 to 3519 are relevant to the check conditions before automatic reclosure of the circuit breaker.
When setting the parameters for the internal automatic reclosing function (Section 2.17.2), it is decided with
which automatic reclosing cycle synchronism and voltage check should be carried out.
Address 3510 Op.mode with AR determines whether closing under asynchronous system conditions is
allowed for automatic reclosure. Set this parameter to with T-CB close to allow asynchronous closing; the
relay will then consider the circuit breaker closing time before determining the correct instant for the close com-
mand. Remember that closing under asynchronous system conditions is allowed only if the circuit breaker
closing time is set correctly (see above under „Preconditions")! If you wish to permit automatic reclosure only
under synchronous system conditions, set this address to w/o T-CB close.
The permissible difference between the voltages is set in address 3511 AR maxVolt.Diff. The setting is
applied in Volts secondary. This value can be entered as a primary value when parameterising with a PC and
DIGSI. Depending on the VT connection these are phase-to-earth voltages or phase-to-phase voltages.
The permissible frequency difference between the voltages is set in address 3512 AR maxFreq.Diff, the
permissible phase angle difference in address 3513 AR maxAngleDiff.
The further release conditions for automatic reclosing are set at addresses 3515 to 3519.
The following addresses mean:
3515 AR SYNC-CHECK
3516 AR Usy1<Usy2>
3517 AR Usy1>Usy2<
3518 AR Usy1<Usy2<
3519 AR OVERRIDE
The five possible release conditions are independent of one another and can be combined.
Synchronism conditions for manual closure and control command
Addresses 3530 to 3539 are relevant to the check conditions before manual closure and closing via control
command of the circuit breaker. When setting the general protection data (Power System Data 2, Section
2.1.4.1) it was already decided at address 1151 whether synchronism and voltage check should be carried out
before manual closing. With the following setting in address SYN.MAN.CL = w/o Sync-check, no checks are
performed before manual closing.
Note
If parameter 1151 SYN.MAN.CL is set to with Sync-check or w/o Sync-check, it is recommended to set
the software filter time under DIGSI 4 for the binary input 356 „>Manual Close" to 50 ms.
356
both measuring points U
sy1
Thr., address 3503); the synchronism conditions are checked, i.e. AR
maxVolt.Diff (address 3511), AR maxFreq.Diff (address 3512) and
AR maxAngleDiff (address 3513). This parameter can only be altered
with DIGSI under Additional Settings;
must be de-energised (Dead Volt. Thr.,
the measuring point U
sy1
address 3502), measuring point U
Thr., address 3503) ;
must be energised (Live Volt. Thr., address
the measuring point U
sy1
3503), measuring point U
address 3502);
both measuring points U
sy1
Thr., address 3502);
automatic reclosure is released without any check.
must be energised (Live Volt.
and U
sy2
must be energised (Live Volt.
sy2
must be de-energised (Dead Volt. Thr.,
sy2
must be de-energised (Dead Volt.
and U
sy2
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011