Technical Data
4.1 General
EMC Tests for Immunity (type tests)
Standards:
High-frequency test
IEC 60255-22-1, Class III
and VDE 0435 Section 303, Class III
Electrostatic Discharge
IEC 60255-22-2, Class IV
and IEC 61000-4-2, Class IV
Irradiation with HF field, frequency sweep
IEC 60255-22-3, Class III
IEC 61000-4-3, Class III
IEEE Std C37.90.2-2004
Irradiation with HF field, single frequencies
IEC 60255-22-3, IEC 61000-4-3, Class III,
IEEE Std C37.90.2
– amplitude modulated
– pulse modulated
Fast transient disturbances/
Burst IEC 60255-22-4 and IEC 61000-4-4, Class IV
High energy surge voltages (SURGE),
IEC 61000-4-5 installation Class 3
- Auxiliary voltage
- Analog measuring inputs, binary inputs, relay outputs
Line conducted HF, amplitude modulated
IEC 61000-4-6, Class III
Power system frequency magnetic field
IEC 60255-6
IEC 61000-4-8, Class IV
Oscillatory Surge Withstand Capability
IEEE Std C37.90.1
Fast Transient Surge Withstand Cap.
IEEE Std C37.90.1
Radiated Electromagnetic Interference
IEEE Std C37.90.2-2004
Damped oscillations IEC 60694, IEC 61000-4-18
580
IEC 60255-6 and -22, (product standards)
EN 61000-6-2 (generic standard) VDE 0435 part 301DIN VDE
0435-110
VDE 0435 part 301 DIN VDE 0435-110
2,5 kV (peak); 1 MHz; τ = 15 µs; 400 surges per s; test duration
2 s; R
= 200 Ω
i
8 kV contact discharge; 15 kV air discharge, both polarities;
150 pF; R
= 330 Ω
i
10 V/m and 20 V/m; 80 MHz to 1000 MHz; 80 % AM; 1 kHz
10 V/m; 800 MHz to 960 MHz; 80 % AM; 1 kHz
20 V/m; 1,4 GHz to 2,0 GHz; 80 % AM; 1 kHz
20 V/m; 80 MHz; 160 MHz; 450 MHz; 900 MHz; 80 % AM;
1kHz;
duty cycle > 10 s
35 V/m; 900 MHz; 50 % PM, repetition frequency 200 Hz
4 kV; 5 ns/50 ns; 5 kHz; burst length = 15 ms; repetition rate
300 ms; both polarities; R
Impulse: 1.2 µs / 50 µs
Common mode: 2 kV; 12 Ω; 9 µF
Diff. mode: 1 kV; 2 Ω; 18 µF
Common mode: 2 kV; 42 Ω; 0,5 µF
Diff. mode: 1 kV; 42 Ω; 0,5 µF
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
0,5 mT; 50 Hz,
30 A/m continuous; 300 A/m for 3 s; 50 Hz
2,5 kV (peak); 1 MHz; τ = 15 µs; 400 surges per s; test duration
2 s; R
= 200 Ω
i
4 kV; 5 ns/50 ns; 5 kHz; burst length = 15 ms; repetition rate 300
ms; both polarities: R
= 50 Ω; test duration 1 min.
i
35 V/m; 80 MHz to 1000 MHz; Keying test
2,5 kV (peak value), polarity alternating 100 kHz, 1 MHz, R
200 Ω
C53000-G1176-C169-5, Release date 02.2011
= 50 Ω; test duration 1 min.
i
SIPROTEC, 7SD5, Manual
=
i

Advertisement

Table of Contents
loading