Addr.
Parameter
1731
Op. mode Z4
1732
ZR(Z4)
1741
Op. mode Z5
1742
ZR(Z5)
1751
Op. mode Z1B
1752
ZR(Z1B)
1761
Op. mode Z6
1762
ZR(Z6)
1771A
Mem.Polariz.PhE
1772A
CrossPolarizPhE
1773A
Mem.Polariz.P-P
1774A
CrossPolarizP-P
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
C
Setting Options
Forward
Reverse
Inactive
1A
0.050 .. 200.000 Ω
5A
0.010 .. 40.000 Ω
Forward
Reverse
Inactive
1A
0.050 .. 200.000 Ω
5A
0.010 .. 40.000 Ω
Forward
Reverse
Inactive
1A
0.050 .. 200.000 Ω
5A
0.010 .. 40.000 Ω
Forward
Reverse
Inactive
1A
0.050 .. 200.000 Ω
5A
0.010 .. 40.000 Ω
0.0 .. 100.0 %
0.0 .. 100.0 %
0.0 .. 100.0 %
0.0 .. 100.0 %
Default Setting
Forward
Operating mode Z4
10.000 Ω
ZR(Z4), Impedance Reach
2.000 Ω
Inactive
Operating mode Z5
10.000 Ω
ZR(Z5), Impedance Reach
2.000 Ω
Forward
Operating mode Z1B (ex-
tended zone)
3.000 Ω
ZR(Z1B), Impedance
Reach
0.600 Ω
Inactive
Operating mode Z6
15.000 Ω
ZR(Z6), Impedance Reach
3.000 Ω
15.0 %
Voltage Memory polariza-
tion (phase-e)
15.0 %
Cross polarization (phase-
e)
15.0 %
Voltage Memory polariza-
tion (ph-ph)
15.0 %
Cross polarization (phase-
phase)
Functions
2.5 Distance Protection
Comments
175