Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Appendix
A.7 Settings
Addr.
Parameter
3121
3I0>>
3122
T 3I0>>
3123
3I0>> Telep/BI
3124
3I0>> SOTF-Trip
3125
3I0>> InrushBlk
3126
BLK /1p 3I0>>
3127
Trip 1p 3I0>>
3130
Op. mode 3I0>
3131
3I0>
3131
3I0>
3132
T 3I0>
3133
3I0> Telep/BI
3134
3I0> SOTF-Trip
3135
3I0> InrushBlk
3136
BLK /1p 3I0>
3137
Trip 1p 3I0>
3140
Op. mode 3I0p
3141
3I0p PICKUP
3141
3I0p PICKUP
3142
3I0p MinT-DELAY
3143
3I0p Time Dial
3144
3I0p Time Dial
3145
3I0p Time Dial
3146
3I0p MaxT-DELAY
3147
Add.T-DELAY
3148
3I0p Telep/BI
3149
3I0p SOTF-Trip
3150
3I0p InrushBlk
696
Function
C
Earth Fault O/C
1A
0.05 .. 25.00 A
5A
0.25 .. 125.00 A
Earth Fault O/C
0.00 .. 30.00 sec; ∞
Earth Fault O/C
NO
YES
Earth Fault O/C
NO
YES
Earth Fault O/C
NO
YES
Earth Fault O/C
YES
No (non-dir.)
Earth Fault O/C
YES
NO
Earth Fault O/C
Forward
Reverse
Non-Directional
Inactive
Earth Fault O/C
1A
0.05 .. 25.00 A
5A
0.25 .. 125.00 A
Earth Fault O/C
1A
0.003 .. 25.000 A
5A
0.015 .. 125.000 A
Earth Fault O/C
0.00 .. 30.00 sec; ∞
Earth Fault O/C
NO
YES
Earth Fault O/C
NO
YES
Earth Fault O/C
NO
YES
Earth Fault O/C
YES
No (non-dir.)
Earth Fault O/C
YES
NO
Earth Fault O/C
Forward
Earth Fault O/C
Reverse
Earth Fault O/C
Non-Directional
Earth Fault O/C
Inactive
Earth Fault O/C
1A
0.05 .. 25.00 A
Earth Fault O/C
5A
0.25 .. 125.00 A
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
1A
0.003 .. 25.000 A
Earth Fault O/C
5A
0.015 .. 125.000 A
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
0.00 .. 30.00 sec
Earth Fault O/C
0.05 .. 3.00 sec; ∞
Earth Fault O/C
0.50 .. 15.00 ; ∞
Earth Fault O/C
0.05 .. 15.00 sec; ∞
Earth Fault O/C
0.00 .. 30.00 sec
Earth Fault O/C
0.00 .. 30.00 sec; ∞
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
NO
Earth Fault O/C
YES
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
NO
Earth Fault O/C
YES
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
NO
Earth Fault O/C
YES
Earth Fault O/C
Earth Fault O/C
Setting Options
Default Setting
2.00 A
10.00 A
0.60 sec
NO
NO
NO
YES
YES
Inactive
1.00 A
5.00 A
1.000 A
5.000 A
0.90 sec
NO
NO
NO
YES
YES
Inactive
1.00 A
5.00 A
1.000 A
5.000 A
1.20 sec
0.50 sec
5.00
1.35 sec
5.80 sec
1.20 sec
NO
NO
NO
C53000-G1176-C169-5, Release date 02.2011
Comments
3I0>> Pickup
T 3I0>> Time Delay
Instantaneous trip via Tele-
prot./BI
Instantaneous trip after Switch-
OnToFault
Inrush Blocking
Block 3I0>> during 1pole dead
time
Single pole trip with 3I0>>
Operating mode
3I0> Pickup
3I0> Pickup
T 3I0> Time Delay
Instantaneous trip via Tele-
prot./BI
Instantaneous trip after Switch-
OnToFault
Inrush Blocking
Block 3I0> during 1pole dead
time
Single pole trip with 3I0>
Operating mode
3I0p Pickup
3I0p Pickup
3I0p Minimum Time Delay
3I0p Time Dial
3I0p Time Dial
3I0p Time Dial
3I0p Maximum Time Delay
Additional Time Delay
Instantaneous trip via Tele-
prot./BI
Instantaneous trip after Switch-
OnToFault
Inrush Blocking