Table 3-2
Jumper
X51
X52
X53
Fuse
Table 3-3
Jumper
X40
Depending on the device version, the contacts of some binary outputs can be changed from normally open to
normally closed (see General Diagrams in Section A.2)
• In versions 7SD5***-*D/H/M (housing size
and BO24 (Figure 3-4, slot 19 left and right);
• In versions 7SD5***-*C/G/L (housing size
(Figure 3-4, slot 19 right);
• In versions 7SD5***-*P/R/T (housing size
for the binary output BO24 (Figure 3-4, slot 19 left).
Table 3-4 shows the jumper settings for the contact mode.
Table 3-4
Jumper settings for contact mode of the binary outputs BO16 and BO24 on the input/output board C–I/O-1
Device
Printed Circuit
7SD5***–*
Board
D/H/M
Slot 19 left side
Slot 19 right side
C/G/L
Slot 19 right side
P/R/T
Slot 19 left side
Checking the control voltages of the binary inputs:
BI1 to BI8 (with housing size
BI1 to BI24 (with housing size
put/output module C-I/O-10 up to release /EE "
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
Jumper settings for the nominal voltage of the integrated power supply on the C-I/O-1
input/output board
DC 60 V/110 V/125 V
1-2
1-2 and 3-4
1-2
Jumper settings of the Life Contact on the input/output board C-I/O-1
Open in Quiescent State
(NO)
1-2
For
Jumper
BO 16
X40
BO 24
X40
BO 16
X40
BO 24
X40
1
/
) according to Table 3-5,
2
1
/
depending on version) according to Table 3-7, under margin heading „In-
1
Nominal voltage
DC 110 V/125 V/220 V/250 V
AC 115 V
2-3
2-3
2-3
T2H250V
Closed in Quiescent State
(NC)
2-3
1
/
with 32 binary outputs) this is valid for the binary outputs BO16
1
1
/
with 24 binary outputs) this is valid for the binary output BO16
1
1
/
with 32 binary outputs and command acceleration) this is valid
1
Open in
Quiescent State (NO)
1-2
1-2
1-2
1-2
Mounting and Commissioning
3.1 Mounting and Connections
DC 24 V/48 V
Jumpers X51 to
X53 are not used
T4H250V
Factory Setting
2-3
Closed in
Quiescent State (NC)
2-3
2-3
2-3
2-3
Factory
Setting
1-2
1-2
1-2
1-2
507