Siemens SIPROTEC Manual page 693

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Addr.
Parameter
2514
3I0> Threshold
2515
TM
2516
TT
2517
1pol. Trip
2518
1pol. with 3I0
2519
3pol. Trip
2520
T 3I0> alarm
2530
WI non delayed
2531
WI delayed
2601
Operating Mode
2602
SOTF Time DELAY
2610
Iph>>
2611
T Iph>>
2612
3I0>> PICKUP
2613
T 3I0>>
2614
I>> Telep/BI
2615
I>> SOTF
2620
Iph>
2621
T Iph>
2622
3I0>
2623
T 3I0>
2624
I> Telep/BI
2625
I> SOTF
2630
Iph> STUB
2631
T Iph STUB
2632
3I0> STUB
2633
T 3I0 STUB
2634
I-STUB Telep/BI
2635
I-STUB SOTF
2640
Ip>
2642
T Ip Time Dial
2643
Time Dial TD Ip
2646
T Ip Add
2650
3I0p PICKUP
2652
T 3I0p TimeDial
2653
TimeDial TD3I0p
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
Function
C
Weak Infeed
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
ON
OFF
Weak Infeed
ON
OFF
Weak Infeed
ON
OFF
Weak Infeed
0.00 .. 30.00 sec
Weak Infeed
ON
OFF
Weak Infeed
ON
by receive fail
OFF
Back-Up O/C
ON
Only Emer. prot
OFF
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
1A
0.05 .. 50.00 A; ∞
5A
0.25 .. 250.00 A; ∞
Back-Up O/C
0.00 .. 30.00 sec; ∞
Back-Up O/C
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞
Back-Up O/C
0.00 .. 30.00 sec; ∞
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
Back-Up O/C
1A
0.05 .. 50.00 A; ∞
5A
0.25 .. 250.00 A; ∞
Back-Up O/C
0.00 .. 30.00 sec; ∞
Back-Up O/C
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞
Back-Up O/C
0.00 .. 30.00 sec; ∞
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
Back-Up O/C
1A
0.05 .. 50.00 A; ∞
5A
0.25 .. 250.00 A; ∞
Back-Up O/C
0.00 .. 30.00 sec; ∞
Back-Up O/C
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞
Back-Up O/C
0.00 .. 30.00 sec; ∞
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
Back-Up O/C
1A
0.10 .. 4.00 A; ∞
5A
0.50 .. 20.00 A; ∞
Back-Up O/C
0.05 .. 3.00 sec; ∞
Back-Up O/C
0.50 .. 15.00 ; ∞
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
Back-Up O/C
0.05 .. 3.00 sec; ∞
Back-Up O/C
0.50 .. 15.00 ; ∞
Setting Options
Default Setting
0.50 A
2.50 A
0.40 sec
1.00 sec
ON
ON
ON
10.00 sec
ON
by receive fail
ON
0.00 sec
2.00 A
10.00 A
0.30 sec
0.50 A
2.50 A
2.00 sec
YES
NO
1.50 A
7.50 A
0.50 sec
0.20 A
1.00 A
2.00 sec
NO
NO
1.50 A
7.50 A
0.30 sec
0.20 A
1.00 A
2.00 sec
NO
NO
∞ A
∞ A
0.50 sec
5.00
0.00 sec
∞ A
∞ A
0.50 sec
5.00
Appendix
A.7 Settings
Comments
3I0 threshold for neutral current
pickup
WI delay single pole
WI delay multi pole
Single pole WI trip allowed
Single pole WI trip with 3I0
Three pole WI trip allowed
3I0> exceeded delay for alarm
WI non delayed
WI delayed
Operating mode
Trip time delay after SOTF
Iph>> Pickup
T Iph>> Time delay
3I0>> Pickup
T 3I0>> Time delay
Instantaneous trip via Tele-
prot./BI
Instantaneous trip after Switch-
OnToFault
Iph> Pickup
T Iph> Time delay
3I0> Pickup
T 3I0> Time delay
Instantaneous trip via Tele-
prot./BI
Instantaneous trip after Switch-
OnToFault
Iph> STUB Pickup
T Iph STUB Time delay
3I0> STUB Pickup
T 3I0 STUB Time delay
Instantaneous trip via Tele-
prot./BI
Instantaneous trip after Switch-
OnToFault
Ip> Pickup
T Ip Time Dial
Time Dial TD Ip
T Ip Additional Time Delay
3I0p Pickup
T 3I0p Time Dial
Time Dial TD 3I0p