Siemens SIPROTEC Manual page 359

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Addr.
Parameter
3503
Live Volt. Thr.
3504
Umax
3507
T-SYN. DURATION
3508
T SYNC-STAB
3509
SyncCB
3510
Op.mode with AR
3511
AR maxVolt.Diff
3512
AR maxFreq.Diff
3513
AR maxAngleDiff
3515A
AR SYNC-CHECK
3516
AR Usy1<Usy2>
3517
AR Usy1>Usy2<
3518
AR Usy1<Usy2<
3519
AR OVERRIDE
3530
Op.mode with MC
3531
MC maxVolt.Diff
3532
MC maxFreq.Diff
3533
MC maxAngleDiff
3535A
MC SYNCHR
3536
MC Usy1< Usy2>
3537
MC Usy1> Usy2<
3538
MC Usy1< Usy2<
3539
MC OVERRIDE
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
Setting Options
20 .. 125 V
20 .. 140 V
0.01 .. 600.00 sec; ∞
0.00 .. 30.00 sec
(Setting options depend
on configuration)
with T-CB close
w/o T-CB close
1.0 .. 60.0 V
0.03 .. 2.00 Hz
2 .. 80 °
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
with T-CB close
w/o T-CB close
1.0 .. 60.0 V
0.03 .. 2.00 Hz
2 .. 80 °
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
2.18 Synchronism and Voltage Check (optional)
Default Setting
90 V
Voltage threshold live line / bus
110 V
Maximum permissible voltage
1.00 sec
Maximum duration of synchro-
nism-check
0.00 sec
Synchronous condition stability
timer
None
Synchronizable circuit breaker
w/o T-CB close
Operating mode with AR
2.0 V
Maximum voltage difference
0.10 Hz
Maximum frequency difference
10 °
Maximum angle difference
YES
AR at Usy2>, Usy1>, and Synchr.
NO
AR at Usy1< and Usy2>
NO
AR at Usy1> and Usy2<
NO
AR at Usy1< and Usy2<
NO
Override of any check before AR
w/o T-CB close
Operating mode with Man.Cl
2.0 V
Maximum voltage difference
0.10 Hz
Maximum frequency difference
10 °
Maximum angle difference
YES
Manual Close at Usy2>, Usy1>,
and Synchr
NO
Manual Close at Usy1< and
Usy2>
NO
Manual Close at Usy1> and
Usy2<
NO
Manual Close at Usy1< and
Usy2<
NO
Override of any check before
Man.Cl
Functions
Comments
359