Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Figure A-15
Important! The cable shield must be grounded on the cable side.
In case of an earthing of the current transformers on the busbar side, the current polarity of the device is
changed via the address 0201. This also reverses the polarity of the current input IE or IEE. Therefore the con-
nections of S1 and S2 must be exchanged at Q8 and Q7 when using a toroidal current transformer.
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
Current connections to 3 current transformers with separate earth current transformer
(summation current transformer) prefered for solidly or low-resistive earthed systems.
Appendix
A.3 Connection Examples