Siemens SIPROTEC Manual page 514

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Mounting and Commissioning
3.1 Mounting and Connections
Table 3-11
Jumper
X41
The set nominal current of the current input transformers are checked on the input/output board C-I/O-2. All
jumpers must be set for one nominal current, i.e. one jumper (X61 to X64) for each input transformer and ad-
ditionally the common jumper X60. But: In the version with sensitive earth fault current input (input transformer
T8) there is no jumper X64.
Jumpers X71, X72 and X73 on the input/output board C-I/O-2 are used to set the bus address and must not be
changed. The following table lists the jumper presettings.
Mounting location:
with housing size
with housing size
Table 3-12
Jumper
X71
X72
X73
514
Jumper setting for contact type of binary output BO13
Open in Quiescent State (NO) Closed in Quiescent State (NC)
1-2
1
/
: No. 3 in Figure 3-3, slot 33,
2
1
/
: No. 3 in Figure 3-4, slot 33 right.
1
Jumper settings of Board Address of the input/output board C-I/O-2
Factory Setting
1-2 (H)
1-2 (H)
2-3 (L)
Factory Setting
2-3
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
1-2