Siemens SIPROTEC Manual page 267

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Evaluation of Measurement Quantities
The earth fault differential protection compares the fundamental component of the current flowing in the star-
point connection, which is designated as 3I
the phase currents designated in the following as 3I
3I
' = I
0
SP
3I
" = I
+ I
0
L1
L2
Only 3I
' acts as the tripping effect quantity. During a fault within the protected zone this current is always
0
present.
Figure 2-134
When an earth fault occurs outside the protected zone, a zero sequence current also flows though the phase
current transformers. This is, on the primary side, in counter-phase with the starpoint current and has equal
magnitude. Therefore, both the magnitude of the currents and their phase relationship are evaluated for re-
straint purposes. The following is defined:
A tripping current
I
= |3I
'|
Ref
0
and a stabilisation or restraining current
I
= k · ( |3I
Rest
where k is a stabilisation factor which will be explained below, at first we assume k = 1. I
ping effect quantity, I
To illustrate the effect, have a look at the three important operating conditions with ideal and adapted measured
values:
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
+ I
L3
Principle of restricted earth fault protection
' – 3I
"| – |3I
' + 3I
"| )
0
0
0
0
counteracts this effect.
Rest
2.10 Restricted Earth Fault Protection (optional)
' in the following, with the fundamental component of the sum of
0
". Thus, the following applies (Figure 2-134):
0
Functions
produces the trip-
REF
267

Advertisement

Table of Contents
loading

Table of Contents