Siemens SIPROTEC Manual page 549

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Figure 3-29
Figure 3-30
Polarity check
If the device is connected to voltage transformers, the local measured values already allow a polarity check.
If there are more than two ends, one current path is still tested first. A load current of at least 5 % of the rated
operational current is still required. Any direction is possible, but it must be known.
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
Local measured values in the WEB-Monitor - Examples of plausible measured values
Remote measured values in the WEB-Monitor - Examples of plausible measured values
Mounting and Commissioning
3.3 Commissioning
549