Siemens SIPROTEC Manual page 687

Line differential protection with distance protection
Hide thumbs Also See for SIPROTEC:
Table of Contents

Advertisement

Addr.
Parameter
1123
Angle K0(> Z1)
1124
center phase
1125
C0/C1
1126
RM/RL ParalLine
1127
XM/XL ParalLine
1128
RATIO Par. Comp
1130A
PoleOpenCurrent
1131A
PoleOpenVoltage
1132A
SI Time all Cl.
1133A
T DELAY SOTF
1134
Line Closure
1135
Reset Trip CMD
1136
OpenPoleDetect.
1140A
I-CTsat. Thres.
1150A
SI Time Man.Cl
1151
SYN.MAN.CL
1152
Man.Clos. Imp.
1155
3pole coupling
1156A
Trip2phFlt
1161
VECTOR GROUP U
1162
VECTOR GROUP I
1163
TRANS STP IS
1201
STATE OF DIFF.
1210
I-DIFF>
1213
I-DIF>SWITCH ON
1217A
T-DELAY I-DIFF>
1218
T3I0 1PHAS
1219A
I> RELEASE DIFF
1221
Ic-comp.
1224
IcSTAB/IcN
1233
I-DIFF>>
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
Function
C
P.System Data 2
-180.00 .. 180.00 °
P.System Data 2
unknown/sym.
Phase 1
Phase 2
Phase 3
P.System Data 2
0.01 .. 10.00
P.System Data 2
0.00 .. 8.00
P.System Data 2
0.00 .. 8.00
P.System Data 2
50 .. 95 %
P.System Data 2
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
P.System Data 2
2 .. 70 V
P.System Data 2
0.01 .. 30.00 sec
P.System Data 2
0.05 .. 30.00 sec
P.System Data 2
only with ManCl
I OR U or ManCl
CB OR I or M/C
I or Man.Close
P.System Data 2
CurrentOpenPole
Current AND CB
Pickup Reset
P.System Data 2
OFF
Current AND CB
w/ measurement
P.System Data 2
1A
0.2 .. 50.0 A; ∞
5A
1.0 .. 250.0 A; ∞
P.System Data 2
0.01 .. 30.00 sec
P.System Data 2
with Sync-check
w/o Sync-check
NO
P.System Data 2
(Setting options depend
on configuration)
P.System Data 2
with PICKUP
with TRIP
P.System Data 2
3pole
1pole leading Ø
1pole lagging Ø
P.System Data 2
0 .. 11
P.System Data 2
0 .. 11
P.System Data 2
Solid Earthed
Not Earthed
Diff. Prot
OFF
ON
Diff. Prot
1A
0.10 .. 20.00 A
5A
0.50 .. 100.00 A
Diff. Prot
1A
0.10 .. 20.00 A
5A
0.50 .. 100.00 A
Diff. Prot
0.00 .. 60.00 sec; ∞
Diff. Prot
0.00 .. 0.50 sec; ∞
Dis. General
Diff. Prot
1A
0.10 .. 20.00 A; 0
5A
0.50 .. 100.00 A; 0
Diff. Prot
OFF
ON
Diff. Prot
2.0 .. 4.0
Diff. Prot
1A
0.8 .. 100.0 A; ∞
5A
4.0 .. 500.0 A; ∞
Setting Options
Default Setting
0.00 °
unknown/sym.
0.75
0.00
0.00
85 %
0.10 A
0.50 A
30 V
0.10 sec
0.25 sec
I or Man.Close
CurrentOpenPole
w/ measurement
20.0 A
100.0 A
0.30 sec
NO
None
with TRIP
3pole
0
0
Solid Earthed
ON
0.30 A
1.50 A
0.30 A
1.50 A
0.00 sec
0.04 sec
0.00 A
0.00 A
OFF
2.5
1.2 A
6.0 A
Appendix
A.7 Settings
Comments
Zero seq. comp. angle, higher
zones >Z1
center phase of feeder
Compensation factor C0/C1
Mutual Parallel Line comp. ratio
RM/RL
Mutual Parallel Line comp. ratio
XM/XL
Neutral current RATIO Parallel
Line Comp
Pole Open Current Threshold
Pole Open Voltage Threshold
Seal-in Time after ALL closures
minimal time for line open before
SOTF
Recognition of Line Closures
with
RESET of Trip Command
open pole detector
CT Saturation Threshold
Seal-in Time after MANUAL clo-
sures
Manual CLOSE COMMAND
generation
MANUAL Closure Impulse after
CONTROL
3 pole coupling
Trip type with 2phase faults
Vector group numeral for voltage
Vector group numeral for current
Transformer starpoint is
State of differential protection
I-DIFF>: Pickup value
I-DIFF>: Value under switch on
condition
I-DIFF>: Trip time delay
Delay 1ph-faults (comp/isol. star-
point)
Min. local current to release
DIFF-Trip
Charging current compensation
Ic Stabilising / Ic Nominal
I-DIFF>>: Pickup value
687