Connecting AC Input Power to the Cisco ASR 1002-F Router

All Cisco ASR 1000 Series Router AC power supplies must be connected to a branch circuit that does
Note
not exceed 20 A.
Read the safety warnings before you begin.
Never install an AC power module and a DC power module in the same chassis. Statement 1050
Warning
Installation of the equipment must comply with local and national electrical codes. Statement 1074
Warning
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the
Warning
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority
or an electrician if you are uncertain that suitable grounding is available. Statement 1024
Warning
This unit might have more than one power supply connection. All connections must be removed to
de-energize the unit. Statement 1028
Warning
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that the
protective device is rated not greater than: AC power supplies 20 A and DC power supplies 30 A. Statement
1005
Connecting AC Input Power to the Cisco ASR 1002-F Router
This section provides instructions for installing the AC power supply into the Cisco ASR 1002-F Router.
shows the AC power supply labels. The following image shows the Cisco ASR 1002-F Router AC power
supply.
Figure 137: Cisco ASR 1002-F Router AC Power Supply Labels
1
Cisco ASR 1000 Series Router Hardware Installation Guide
308
Chassis ESD socket
5
Cisco ASR 1002-F Router Overview and Installation
Fan