Omron NV Series Setup Manual page 93

Programmable
Hide thumbs Also See for NV Series:
Table of Contents

Advertisement

Wiring the Power Supply and Serial Communications
RS-485 Connections
Note
RS-485 (+)
RS-485 (−)
Power supply (+)
Power supply (−)
RS-485 (2-wire) cannot be used to connect to a Serial Communications
Board/Unit using the Host Link protocol. Use RS-422A (4-wire).
Connecting to EJ1 Temperature Controllers Using RS-485
EDU in EJI Modular
Temperature Controller
EJ1
EDU
Model
Model with
with
connector
screw
terminal
terminals
block
6
7
+
7
8
-
8
9
+
9
10
-
To 24-V
power supply
Up to 31
Temperature
EDU
Controllers can
be connected.
*1
+
-
+
-
To 24-V
power supply
NV
To 24-V
power supply
(RS-485)
Pin
Signal
1
+
2
3
FG
4
+SD
−SD
5
6
+RD
−RD
7
8
E
*1 Connect a terminating resistance
of 110 to 125 Ω to the last EJ1
Temperature Controller.
Section 4-4
NV
To power
+
supply
+SD
-SD
+RD
-RD
E
73