Error Codes and Countermeasures
126
Code number
NV3W
PTs except
NV3W
ER03
ER0103
ER0303
ER1003
ER1103
ER2503
ER04
ER0304
ER1004
ER1104
ER2504
ER05
ER0205
ER1005
ER2505
ER06
ER2506
ER07
ER2507
ER09
ER2609
ER0A
ER250A
ER0B
ER110B
ER0C
ER110C
ER0F
ER250F
Description
Retries failed
The PLC could not send the data
within the specified number of
retries (possibly caused by
noise).
Controller error
Check the status of the Commu-
nications Unit.
Elements/data
The number of elements or data
don't match
does not match (possibly caused
by noise).
Address range
An address specified in the
error
screen data is beyond the range
supported by the PLC. Check the
manuals for your PLC and spec-
ify an address within the sup-
ported range.
I/O setting error
Correct the I/O tables in the PLC.
Unit number error Check the unit number setting.
Command for-
The data does not match the
mat error
expected command format (pos-
sibly caused by noise).
Address range
The end address (specified
exceeded
address plus number of
accessed words) in the screen
data is beyond the accessible
range in the PLC. Check address
allocations in the screen data.
Too many I/O
There are too many I/O points
points
registered in the PLC. Correct
the settings in the PLC.
Response time-
The response waiting time at the
out
PLC expired (possibly caused by
noise).
Header error
There is an error in the communi-
cations header information at the
PLC (possibly caused by noise).
CPU bus error
Check the connection between
the CPU Unit and CPU Bus Unit
in the PLC and then cycle the
power supply.
I/O duplication
Correct the I/O Unit settings in
the PLC.
I/O bus error
Check the status of the I/O Units
in the PLC.
Necessary items
There is an error in the communi-
not set
cations data at the PLC (possibly
caused by noise).
CPU Bus Unit
Check the status of the CPU Bus
error
Units in the PLC.
Response too
The response at the PLC is
long
longer than the maximum per-
missible length (possibly caused
by noise).
Parameter error
There is an error in the communi-
cations data at the PLC (possibly
caused by noise).
Memory error
There is an error in PLC memory.
Check the PLC.
Section 7-5
Countermeasure