PLC Settings
PLC Setup
Item
Serial Port Tab Page Baud rate
Data length
Stop bits
Parity
Unit No.
1,2,3...
104
CX-Programmer
CP or CJ2:
USB cable
CJ1/CS1 PLC: Programming Device
connecting cable for peripheral
port, or RS-232C cable
Item
7 or 8 bits
1 bit
Even or odd
Use the following procedure.
1. Start the CX-Programmer, and then open the PLC Setup Dialog Box by
double-clicking PLC Settings in the project tree.
2. Click the Serial Port Tab.
3. Make the following settings in the Communications Settings Area.
• Select the Custom Option. (The default is Standard.)
• Set the baud rate. (The default is 9,600.)
• Format = 7,1,E (7-bit data, 1 stop bit, and even parity)
Format = 7,2,E (7-bit data, 2 stop bits, and even parity)
• Select Host Link Mode (the default) as the mode.
Set Host Link and one stop bit for
the serial port communications
conditions.
Transfer
PLC
Setup
Settings
9,600, 19,200, 38,400,
57,600, or 115,200 bps
Must be set to 1 bit.
Set to 0.
Section 6-3
PLC