B8 Energy Saving - YASKAWA VS-616G5 Series Programming Manual

Hide thumbs Also See for VS-616G5 Series:
Table of Contents

Advertisement

B6-04 Dwell Time at Stop
Setting Range:
Factory Default:
Sets the amount of time that the frequency reference "dwells" during deceleration in units of 0.1s.
B7
Droop Control
The Drooping function reduces the motor speed based on the load torque of the motor.
B7-01 Droop Control Gain
Setting Range:
Factory Default:
Parameter b7-01 sets the amount of motor speed reduction when the motor is producing 100% of rated
torque. The actual amount of motor speed reduction is based on the ratio of the amount of motor
torque and the maximum output frequency (E1-04).
B7-02 Droop Control Delay Time
Setting Range:
Factory Default:
Parameter b7-02 sets the response time for the drooping function. Decreasing the droop delay time,
will cause the response to become quicker; however, instability may occur.
B8
Energy Saving
This feature can save energy during operation under lightly loaded conditions, by decreasing output
voltage, energy-saving operation is made available. Energy saving control is enabled by a multi-func-
tion contact input, when control mode selection (A1-02) is set to "0" (V/f Control) or "1" (V/f w/PG
Fdbk).
Parameters B8-03, B8-04 and B8-05 are for energy savings in the vector modes. B8-01 and B8-02 are
only functional in the V/f modes via a multi-function input command. Parameters B8-03, B8-04 and
B8-05 are for automatic energy savings in the vector modes.
B8-01 Energy Saving Gain
Setting Range:
Factory Default:
The output voltage during energy-saving operation is the product of the normal V/f settings (El-03 to
E1-10) and the energy saving gain. The output voltage decreases and recovers in the voltage recovery
time (L2-04). As the energy saving gain increases, the output voltage increases also. This feature is
only enabled by a multi-function contact input.
VS-616G5 Programming Manual
0.0 to 10.0s
0.0s
0.0 to 100.0
0.0
0.03 to 2.00
0.05
0 to 100%
80%
Section B: Application Parameters
B7 Droop Control and B8 Energy Saving
Dwell Time @Stop
Droop Quantity
Droop Delay Time
Energy Save Gain
Open Loop
Flux
V/f
V/f w/PG
Vector
Vector
A
A
A
A
-
-
-
A
-
-
-
A
A
A
-
-
27